If a gas leak detection system based on 4-20 mA current loop is to work autonomously, the detectors can be supplemented with the NZ425 or NZ425-DIN power supply.
The NZ425 power supply is designed to provide supply voltage to one or maximum 4 gas detector units.
The power supply also allows to process the output signal from the detectors. Relays, which are contained on the PCB, provide galvanic isolation of the detector power output.
In the power supply a delay in processing the signal from the detector can be set by the user. User can set up number of connected sensors and level for every output relay.
The version NZ425-DIN is different in mechanical design - it is not set in a plastic box. It can be mounted on a DIN rail in a switchboard using its plastic holder. Otherwise, both versions are identical.
Basic technical parameters
Supply voltage | 230 V AC |
Mechanical dimensions NZ425 | 163x133x77 mm (without the holder) |
Mechanical dimensions NZ425-DIN | 154x92x73 mm |
Power consumption | 16VA max |
Output voltage | 24V DC / 0.4A non-stabilized |